TECHNICAL DATA
General
Standards
IEC/EN 60947, VDE 0660,UL, CSA
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureStorage
– 40 – 80 °C
Ambient temperatureOpen
-25 – +55 °C
Ambient temperatureEnclosed
– 25 – 40 °C
Mounting position
Direction of incoming supply
as required
Degree of protectionDevice
IP20
Degree of protectionTerminations
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27
25 g
Altitude
Max. 2000 m
Terminal capacity main cableScrew terminalsSolid
1 x (1 – 6)
2 x (1 – 6) mm2
Terminal capacity main cableScrew terminalsFlexible with ferrule to DIN 46228
1 x (1 – 6)
2 x (1 – 6) mm2
Terminal capacity main cableScrew terminalsSolid or stranded
18 – 10 AWG
Terminal capacity main cableScrew terminalsStripping length
10 mm
Specified tightening torque for terminal screwsMain cable
1.7 Nm
Specified tightening torque for terminal screwsControl circuit cables
1 Nm
Main conducting paths
Rated impulse withstand voltage [Uimp]
6000 V AC
Overvoltage category/pollution degree
III/3
Rated operational voltage [Ue ]
690 V AC
Rated uninterrupted current = rated operational current [Iu = Ie ]
2.5 A
Rated frequency [f]
40 – 60 Hz
Current heat loss (3 pole at operating temperature)
5.16 W
Impedance per pole
270 mΩ
Lifespan, mechanical [Operations]
0.1 x 106
Lifespan, electrical (AC-3 at 400 V)Lifespan, electrical [Operations]
0.1 x 106
Max. operating frequency
40 Ops/h
Short-circuit ratingDCShort-circuit rating
60 kA
Short-circuit ratingDCNotes
up to 250 V
Motor switching capacityAC-3 (up to 690V)
2.5 A
Motor switching capacityDC-5 (up to 250V)
2.5 (3 contacts in series) A
Trip blocks
Temperature compensationto IEC/EN 60947, VDE 0660
– 5…40 °C
Temperature compensationOperating range
– 25…55 °C
Temperature compensation residual error for T > 40 °C
≦ 0.25 %/K
Setting range of overload releases
0.6 – 1 x Iu
short-circuit release
Basic device, fixed: 15.5 x Iu
Short-circuit release tolerance
± 20%
Phase-failure sensitivity
IEC/EN 60947-4-1, VDE 0660 Part 102
Rating data for approved types
Switching capacityMaximum motor ratingThree-phase200 V
208 V
0.5 HP
Switching capacityMaximum motor ratingThree-phase230 V
240 V
0.5 HP
Switching capacityMaximum motor ratingThree-phase460 V
480 V
1 HP
Switching capacityMaximum motor ratingThree-phase575 V
600 V
1.5 HP
Switching capacityMaximum motor ratingSingle-phase230 V
240 V
0.17 HP
Short Circuit Current Rating, type E240 V
65 kA
Short Circuit Current Rating, type E480 Y / 277 V
65 kA
Short Circuit Current Rating, type E600 Y / 347 V
50 kA
Short Circuit Current Rating, type EAccessories required
BK25/3-PKZ0-E
Short Circuit Current Rating, group protection600 V High FaultSCCR (fuse)
50 kA
Short Circuit Current Rating, group protection600 V High Faultmax. Fuse
600 A
Short Circuit Current Rating, group protection600 V High FaultSCCR (CB)
50 kA
Short Circuit Current Rating, group protection600 V High Faultmax. CB
600 A
A26-30-01 ABB Contactor
A110-30-11 ABB Contactor
ALLEN BRADLEY 100-C09D10 Contactor
23 3M SCOTCH CINTA AISLANTE AUTOSOLDABLE
CINTA DE EMPAQUE TRANSPARENTE 48X35M
Schneider Electric GV2ME10 Guardamotor
Juego de machos de roscar HSS,M10 1.5mm
CINTA TEFLON PTFE SHURTAPE
SCHNEIDER ELECTRIC GV3ME80 GUARDAMOTOR
Schneider Electric LC1D09M7 - Contactor
SCHNEIDER ELECTRIC LADN22C BLOQUE DE CONTACTO
MS116-6.3 ABB Guardamotor
Schneider Electric LC1D18 Conntactor Tesys
LANN20N SCHNEIDER ELECTRIC CONTACTO AUXILIAR
CSQ LC1D32 - Contactor
ABB CAL 18-11 Contacto auxiliar lateral
RELE TEMPORIZADOR FINDER 85.02.8.240.0000
EATON MOELLER PKZM0-25 - GUARDAMOTOR 












Valoraciones
No hay valoraciones aún.